Model PDP Series 200 maxDPU4E Hardware Guide
During the restart, the serial port LEDs provide an indication of the
health of the database image. If both LEDs are green, the database is
good. The DPU will not load a database that it determines to be bad.
Besides a bad database, there is one other condition that will prevent a
saved database from being reloaded. If the maxNET IP address that is set
in the switches differs from the address saved in the database, the
database will not be loaded and the DPU will come up without a
database. This is indicated by the Serial Port 1 LED turning yellow. This
condition could occur if, for example, you removed a DPU from one slot
and placed it into another slot that had its address switches set
differently.
LED Indications While Flashing a New Software Image
Setting the mode switch to “E” and then pressing Reset causes the DPU
to enter a mode where it is ready for a network software download. Both
the CP and IOM firmware are upgradable from a maxSTATION. When
the DPU is ready to accept the download, the Network A, B and Backup
LEDs quickly flash yellow. When the CP download is in progress the
three LEDs turn red. At the end of the download they return to flashing
yellow.
When the IOM firmware is being reprogrammed, the IOM's LEDs will
flash green. When the IOM update is completed and error free, the LEDs
will flash yellow. At that time the CP will begin its flashing process.
Metso Automation MAX Controls Inc. 278590